BGMD-TSC dynamic filter compensation component
It is composed of the silicon-controlled switching switch, harmonic adjustment reactor and power capacitor. The reactance ratio of the harmonic adjustment reactor is optional between 5% and 14%.
Technical parameters
Structure features
● Design case
Specification model
● Model selection table of BGMD-TSC three-phase dynamic filter
Transformer capacity KVA | Recommended compensation capacity (kvar) | Component model | Group mode | Minimum cabinet size |
---|---|---|---|---|
200 KVA | 75 KVAR | BGMD-TSC7-S-75/3-400V | 25KVAR*3 | 800*800*2200 |
315 KVA | 100 KVAR | BGMD-TSC7-S-100/4-400V | 25KVAR*4 | 800*800*2200 |
400 KVA | 125 KVAR | BGMD-TSC7-S-125/3-400V | 25KVAR+50KVAR*2 | 800*800*2200 |
500 KVA | 175 KVAR | BGMD-TSC7-S-175/4-400V | 25KVAR+50KVAR*3 | 800*800*2200 |
630 KVA | 200 KVAR | BGMD-TSC7-S-200/5-400V | 25KVAR*2+50KVAR*3 | 800*800*2200 |
800 KVA | 250 KVAR | BGMD-TSC7-S-250/6-400V | 25KVAR*2+50KVAR*4 | 800*800*2200 |
1000 KVA | 350 KVAR | BGMD-TSC7-S-350/5-400V | 25KVAR*2+50KVAR*6 | 1000*800*2200 |
1250 KVA | 200 KVAR * 2 | BGMD-TSC7-S-200/5-400V * 2 | 50KVAR*8 | 800*800*2200 |
1600 KVA | 250 KVAR * 2 | BGMD-TSC7-S-250/5-400V * 2 | 50KVAR*10 | 800*800*2200 |
2000 KVA | 350 KVAR * 2 | BGMD-TSC7-S-350/7-400V * 2 | 50KVAR*14 | 1000*800*2200 |
2500 KVA | 300 KVAR * 3 | BGMD-TSC7-S-300/6-400V * 3 | 50KVAR*18 | 1000*800*2200 |
Transformer capacity KVA | Recommended compensation capacity (kvar) | Component model | Group mode | Minimum cabinet size |
---|---|---|---|---|
200 KVA | 75 KVAR | BGMD-TSC14-S-75/3-400V | 25KVAR*3 | 800*800*2200 |
315 KVA | 100 KVAR | BGMD-TSC14-S-100/4-400V | 25KVAR*4 | 800*800*2200 |
400 KVA | 125 KVAR | BGMD-TSC14-S-125/3-400V | 25KVAR+50KVAR*2 | 800*800*2200 |
500 KVA | 175 KVAR | BGMD-TSC14-S-175/4-400V | 25KVAR+50KVAR*3 | 800*800*2200 |
630 KVA | 200 KVAR | BGMD-TSC14-S-200/5-400V | 25KVAR*2+50KVAR*3 | 800*800*2200 |
800 KVA | 250 KVAR | BGMD-TSC14-S-250/6-400V | 25KVAR*2+50KVAR*4 | 800*800*2200 |
1000 KVA | 350 KVAR | BGMD-TSC14-S-350/5-400V | 25KVAR*2+50KVAR*6 | 1000*800*2200 |
1250 KVA | 200 KVAR * 2 | BGMD-TSC14-S-200/5-400V * 2 | 50KVAR*8 | 800*800*2200 |
1600 KVA | 250 KVAR * 2 | BGMD-TSC14-S-250/5-400V * 2 | 50KVAR*10 | 800*800*2200 |
2000 KVA | 350 KVAR * 2 | BGMD-TSC14-S-350/7-400V * 2 | 50KVAR*14 | 1000*800*2200 |
2500 KVA | 300 KVAR * 3 | BGMD-TSC14-S-300/6-400V * 3 | 50KVAR*18 | 1000*800*2200 |
Model selection table of BGMD-TSC single-phase dynamic filter compensation components (SCR + reactor + capacitor)
System voltage 400V, reactance ratio 14%, tuning frequency 134Hz, suppression of harmonics for 3 times; capacitor rated voltage UN=525V;
Output capacity KVAR | Reactor model | Group mode | Remark |
---|---|---|---|
15 KVAR | BGMD-TSC14-D-15/3-400V | 5KVAR*3 |
Phase-splitting compensation capacity (KVAR)
= total compensation capacity of transformer
(KVAR)*(30%~40%)
|
30 KVAR | BGMD-TSC14-D-30/3-400V | 10KVAR*3 | |
45 KVAR | BGMD-TSC14-D-45/3-400V | 15KVAR*3 | |
60 KVAR | BGMD-TSC14-D-60/6-400V | 10KVAR*6 | |
75 KVAR | BGMD-TSC14-D-75/6-400V | 10KVAR*3+15KVAR*3 | |
90 KVAR | BGMD-TSC14-D-90/6-400V | 15KVAR*6 | |
105 KVAR | BGMD-TSC14-D-105/6-400V | 10KVAR*6+15KVAR*3 | |
120 KVAR | BGMD-TSC14-D-120/9-400V | 10KVAR*3+15KVAR*6 | |
135 KVAR | BGMD-TSC14-D-135/9-400V | 15KVAR*9 | |
150 KVAR | BGMD-TSC14-D-150/12-400V | 10KVAR*6+15KVAR*6 | |
165 KVAR | BGMD-TSC14-D-165/12-400V | 10KVAR*3+15KVAR*9 | |
180 KVAR | BGMD-TSC14-D-180/12-400V | 15KVAR*12 | |
195 KVAR | BGMD-TSC14-D-195/15-400V | 10KVAR*6+15KVAR*9 |