Home Page > Solutions  > Low voltage dynamic reactive compensation solution

Introduction to the scheme

The low voltage dynamic power factor correction solution is mainly achieved by BGMD-TSC dynamic filter compensation components, which is composed of the thyristor switch, harmonic adjustment reactor and power capacitor. The reactance ratio of the harmonic adjustment reactor is optional between 5% and 14% and the controller is selected from BGMD-FR12 or BGMD-FR18 series.
 
 
The filter compensation components can be classified into those with reactance ratio 7% and 14% according to the system characteristics and compensation requirements.
TSC filter compensation component series with the reactance ratio of 7% and tuning frequency of 189Hz can effectively suppress the harmonic pollutions for 5 times and above while providing reliable reactive compensation.
TSC filter compensation component series with the reactance ratio of 14% and tuning frequency of 134Hz can effectively suppress the harmonic pollutions for 3 times and above while providing reliable reactive compensation.

Application domain

Application scenarios
In this solution, thyristor silicon-controlled switch is mainly used as the switching component. The solution, with the zero switch principle and without impact or surge in switching, applies to the power distribution system with large load fluctuations as well as the power distribution systems for centralized compensation, on-site compensation, box transformer substation compensation and rural power network renovation.
 
 
Compensation effect
The stable and reliable compensation system can meet the reactive compensation requirements in dynamic conditions. Due to the use of thyristor module without mechanical contact as the switching switch, there is no surge or impact at the moment of switching.

Related case

Scheme selection如需更详细技术资料,请致电021-62603561

●  Model selection table of BGMD-TSC three-phase dynamic filter compensation components (silicon-controlled switch + reactor + capacitor)

System voltage 400V, reactance ratio 7%, tuning frequency 189Hz, suppression of harmonics for 5 times and 7 times; capacitor rated voltage UN=480V;
     
SCR dynamic switching applies to the power supply system with frequently changing load, such as welding equipment;
 
Transformer capacity KVA Recommended compensation capacity (kvar) Component model Group mode Minimum cabinet size
200 KVA 75 KVAR BGMD-TSC7-S-75/3-400V 25KVAR*3 800*800*2200
315 KVA 100 KVAR BGMD-TSC7-S-100/4-400V 25KVAR*4 800*800*2200
400 KVA 125 KVAR BGMD-TSC7-S-125/3-400V 25KVAR+50KVAR*2 800*800*2200
500 KVA 175 KVAR BGMD-TSC7-S-175/4-400V 25KVAR+50KVAR*3 800*800*2200
630 KVA 200 KVAR BGMD-TSC7-S-200/5-400V 25KVAR*2+50KVAR*3 800*800*2200
800 KVA 250 KVAR BGMD-TSC7-S-250/6-400V 25KVAR*2+50KVAR*4 800*800*2200
1000 KVA 350 KVAR BGMD-TSC7-S-350/5-400V 25KVAR*2+50KVAR*6 1000*800*2200
1250 KVA 200 KVAR * 2 BGMD-TSC7-S-200/5-400V * 2 50KVAR*8 800*800*2200
1600 KVA 250 KVAR * 2 BGMD-TSC7-S-250/5-400V * 2 50KVAR*10 800*800*2200
2000 KVA 350 KVAR * 2 BGMD-TSC7-S-350/7-400V * 2 50KVAR*14 1000*800*2200
2500 KVA 300 KVAR * 3 BGMD-TSC7-S-300/6-400V * 3 50KVAR*18 1000*800*2200

 

 

System voltage 400V, reactance ratio 14%, tuning frequency 134Hz, suppression of harmonics for 3 times; capacitor rated voltage UN=525V;
     
SCR dynamic switching applies to the power supply system with frequently changing load, such as welding equipment;
 
Transformer capacity KVA Recommended compensation capacity (kvar) Component model Group mode Minimum cabinet size
200 KVA 75 KVAR BGMD-TSC14-S-75/3-400V 25KVAR*3 800*800*2200
315 KVA 100 KVAR BGMD-TSC14-S-100/4-400V 25KVAR*4 800*800*2200
400 KVA 125 KVAR BGMD-TSC14-S-125/3-400V 25KVAR+50KVAR*2 800*800*2200
500 KVA 175 KVAR BGMD-TSC14-S-175/4-400V 25KVAR+50KVAR*3 800*800*2200
630 KVA 200 KVAR BGMD-TSC14-S-200/5-400V 25KVAR*2+50KVAR*3 800*800*2200
800 KVA 250 KVAR BGMD-TSC14-S-250/6-400V 25KVAR*2+50KVAR*4 800*800*2200
1000 KVA 350 KVAR BGMD-TSC14-S-350/5-400V 25KVAR*2+50KVAR*6 1000*800*2200
1250 KVA 200 KVAR * 2 BGMD-TSC14-S-200/5-400V * 2 50KVAR*8 800*800*2200
1600 KVA 250 KVAR * 2 BGMD-TSC14-S-250/5-400V * 2 50KVAR*10 800*800*2200
2000 KVA 350 KVAR * 2 BGMD-TSC14-S-350/7-400V * 2 50KVAR*14 1000*800*2200
2500 KVA 300 KVAR * 3 BGMD-TSC14-S-300/6-400V * 3 50KVAR*18 1000*800*2200

 

 

Model selection table of BGMD-TSC single-phase dynamic filter compensation components (SCR + reactor + capacitor)

System voltage 400V, reactance ratio 14%, tuning frequency 134Hz, suppression of harmonics for 3 times; capacitor rated voltage UN=525V;

Output capacity KVAR Reactor model Group mode Remark
15 KVAR BGMD-TSC14-D-15/3-400V 5KVAR*3
Phase-splitting compensation capacity (KVAR)
= total compensation capacity of transformer 
(KVAR)*(30%~40%)
30 KVAR BGMD-TSC14-D-30/3-400V 10KVAR*3
45 KVAR BGMD-TSC14-D-45/3-400V 15KVAR*3
60 KVAR BGMD-TSC14-D-60/6-400V 10KVAR*6
75 KVAR BGMD-TSC14-D-75/6-400V 10KVAR*3+15KVAR*3
90 KVAR BGMD-TSC14-D-90/6-400V 15KVAR*6
105 KVAR BGMD-TSC14-D-105/6-400V 10KVAR*6+15KVAR*3
120 KVAR BGMD-TSC14-D-120/9-400V 10KVAR*3+15KVAR*6
135 KVAR BGMD-TSC14-D-135/9-400V 15KVAR*9
150 KVAR BGMD-TSC14-D-150/12-400V  10KVAR*6+15KVAR*6
165 KVAR BGMD-TSC14-D-165/12-400V 10KVAR*3+15KVAR*9
180 KVAR BGMD-TSC14-D-180/12-400V 15KVAR*12
195 KVAR BGMD-TSC14-D-195/15-400V 10KVAR*6+15KVAR*9

 